504. Conducting cables supplying mobile electrical equipment at a voltage of more than 300 V, including grounding conductors, shall meet CSA Standard C-22.2 No. 96M1989 Portable Power Cables, and the following specifications:
(1)  the cable-filling material shall be rubber or any other synthetic material with similar properties;
(2)  each phase conductor shall be of a gauge equal to or larger than No. 8 AWG;
(3)  the grounding conductors shall be uninsulated or shall be covered with a semi-conducting insulation or shall have a total conductance equal to or greater than 60% of that of the largest phase conductor; each grounding conductor shall be equal to or larger than No. 8 AWG;
(4)  where the insulated monitoring conductor in a cable supplying energy to a single piece of equipment is supplied to it by a separate power source, the energy supplying the equipment shall be disconnected when the conductors of the separate energy source are cut or when a grounding conductor is broken.